Tewksbury Massachusetts, This Navien High Efficient NCB-240E combination 3 zone heating system and tankless water heater was installed incorrectly in 2017 by some other company that is no longer in business. This client had combustible gas leaking internally caused by improper venting of this unit. We corrected the exhaust vent line and air intake line so there is proper spacing between them. Then we removed the failed heat exchanger & burner assembly. Installed new heat exchanger with new burner & igniters. Repiped the corroded piping below boiler circulator pumps, and added proper purge point. Unit now running Ike brand new. It’s very important to install these units to manufactures specifications. If not they will fail prematurely.
So [Music] All right here we are today Replacing a failed heat exchanger in a Navian unit that Someone else installed and didn’t Install it properly So michael and i are going to replace This heat exchanger And get this thing back to proper Working order and fix up all the Mistakes of the previous installer Where’s the failed heat exchanger This gasket was no good and the burner Was Falling down and melting down into the Igniters Your head’s in the way the shadow Navi and i’d like to know how you’re Supposed to clean That on these systems All right michael’s got the heat Exchanger out And he’s transferring The inducer motor and stuff over to the New heat exchanger right now You